site logo
进行绿色能源到底

2V TUBULAR GEL SERIES VRLA BATTERY

2V TUBULAR GEL SERIES VRLA BATTERY
  • 2V TUBULAR GEL SERIES VRLA BATTERY

2V TUBULAR GEL SERIES VRLA BATTERY


The  OPzV  series  adopts  an  Immobilized  Gel  and  Tubular  Positive  Plate technology.  It  offers  high  reliability  and  stable  performance.  By  using  die- casted  positive  grid  and  patented  active  material  formula,  it  exceeds  the DIN standard values and offer 20+ years design life in float service. It is very suitable  for  cyclic  use  under  extreme  operating  conditions.  This  series  is recommended for telecom outdoor applications, renewable energy systems and other harsh environment applications.


SPECIFICATIONS
DIMENSIONS
DISCHARGE TABLE
CHARACTERISTICS
Nominal Voltage (V) 2
Designed Floating Life (20oC) 20+ Years
Nominal Capacity (20oC) 1000 Ah @ C10 (to 1.80Vpc)
Demensions L233mm×W210mm×H681mm
Approx. Weight 73.2 kg (161.4 lbs)
Terminal Type Female Copper Insert M8 (torque:10~12N.m)
Internal Resistance Approx. 0.37mOhm (fully charged @ 20°C)
Max. Charge Current 200 A
Max. Discharge Current (5S) 2500 A
Short Circuit Current 5400 A
Self Discharge Approx. 2% per month @ 20°C
Ambient Temperature Discharge: -40~65°C Charge:     -30~65°C Storage:    -25~45°C
Float Charge Voltage (20~25oC) 2.25-2.29V (-3mV / oC/ cell)
Equalize Charge Voltage (20~25°C) 2.35-2.40V (-5mV / oC/ cell)
Container Material ABS(UL94-V0 optional)
BATTERY DISCHARGE TABLE   
Constant Current Discharge Characteristics: Amps (20°C)
F . V / T im e 1 0 m in 1 5 m in 3 0 m in 1 h 2 h 3 h 5 h 8 h 1 0 h
1 . 9 0 V 3 5 8 3 4 8 3 2 5 2 7 3 2 3 4 1 9 6 1 4 5 1 0 4 8 5 . 8
1 . 8 7 V 4 8 7 4 5 5 4 0 3 3 1 9 2 6 1 2 1 6 1 5 7 1 1 0 9 0 . 7
1 . 8 5 V 5 6 1 5 1 4 4 4 2 3 4 8 2 8 8 2 3 2 1 6 8 1 1 5 9 4 . 2
1 . 8 3 V 6 5 3 5 7 2 4 7 8 3 8 4 3 0 8 2 4 5 1 7 2 1 1 9 9 6 . 0
1 . 8 0 V 7 3 1 6 6 3 5 3 5 4 2 3 3 2 5 2 5 7 1 7 5 1 2 1 9 8 . 0
1 . 7 5 V 7 7 5 7 2 8 6 2 7 4 6 0 3 3 9 2 6 5 1 7 8 1 2 3 1 0 1
1 . 7 0 V 8 4 3 8 0 0 6 8 9 4 8 6 3 5 2 2 7 0 1 8 1 1 2 4 1 0 3
1 . 6 5 V 9 8 5 9 0 0 7 5 1 5 1 7 3 6 2 2 7 4 1 8 5 1 2 6 1 0 5
1 . 6 0 V 1 0 7 2 9 8 8 7 9 6 5 3 3 3 6 9 2 7 9 1 8 9 1 2 9 1 0 7

Constant Power Discharge Characteristics: W/cell (20°C)
F .V /T im e 1 0 m in 1 5 m in 3 0 m in 1 h 2 h 3 h 5 h 8 h 1 0 h
1 .9 0 V 6 9 1 6 7 3 6 3 3 5 3 6 4 6 2 3 9 0 2 9 1 2 0 9 1 7 3
1 .8 7 V 9 2 3 8 6 5 7 7 2 6 1 5 5 1 1 4 2 5 3 1 3 2 2 0 1 8 2
1 .8 5 V 1 0 4 7 9 6 3 8 3 5 6 6 4 5 5 6 4 5 3 3 3 0 2 2 9 1 8 7
1 .8 3 V 1 2 0 6 1 0 6 1 8 9 3 7 2 4 5 8 8 4 7 3 3 3 3 2 3 2 1 8 9
1 .8 0 V 1 3 3 0 1 2 1 2 9 8 6 7 8 8 6 1 3 4 9 1 3 3 7 2 3 4 1 9 1
1 .7 5 V 1 3 8 8 1 3 1 0 1 1 4 1 8 4 6 6 3 1 4 9 7 3 3 9 2 3 5 1 9 4
1 .7 0 V 1 4 8 9 1 4 1 9 1 2 3 6 8 8 2 6 4 8 5 0 1 3 4 1 2 3 7 1 9 7
1 .6 5 V 1 7 0 8 1 5 7 3 1 3 2 6 9 2 5 6 5 8 5 0 4 3 4 4 2 3 8 1 9 8
1 .6 0 V 1 8 2 3 1 6 9 1 1 3 8 0 9 3 8 6 6 2 5 0 5 3 4 7 2 4 0 2 0 0

PARAMETERS FOR SOLAR & WIND APPLICATIONS
Long time discharge capacity for Solar & Wind applications
Capacity C20
(Ah)
C24
(Ah)
C48
(Ah)
C72
(Ah)
C100
(Ah)
C120
(Ah)
C240
(Ah)
OPzV2-1000 1080 1120 1220 1260 1275 1290 1316
Final Voltage 1.80V 1.85V

Solar & Wind applications parameters settings
Over voltage disconnect: 2.45±0.01V/cell   @ 20~25°C
Regulation/equalize voltage: 2.40±0.01V/cell   @ 20~25°C
Array roconnection voltage: 2.25±0.005V/cell @ 20~25°C
Float voltage setting: 2.27±0.005V/cell @ 20~25°C
Low voltage alarm voltage: 1.95±0.005V/cell @ 20~25°C
Low voltage disconnect: 1.90±0.005V/cell @ 20~25°C
Load reconnect voltage: 2.09±0.01V/cell   @ 20~25°C
Temp. compensate coefficienty: -5mV/cell/°C